Underfloor heating promises a warmer, clutter-free home without radiators along the walls, but the decision between wet and electric systems, and whether UFH is genuinely cost-effective, depends heavily on how you use the space, what heat source you have, and what the floor construction is.

For a typical UK kitchen-diner of 25 m², electric mat UFH costs roughly £1,200–£2,500 installed, while a wet system serving the same zone from an existing combi boiler costs £2,500–£4,500. Neither figure tells the whole story without running costs, so this guide covers both.

Wet vs Electric Underfloor Heating

The most important decision is which system type is appropriate for your situation.

Electric underfloor heating

Electric UFH uses resistance heating cables or pre-made mats laid beneath the floor finish. Installation is relatively simple, there is no pipework, no manifold, and no need to connect to the boiler circuit. A qualified electrician (Part P notified work) connects the mat to its thermostat and the consumer unit.

Best suited to:

  • Bathrooms, ensuites, and small tiled areas where you want a comfort heat boost
  • Retrofits where disruption to screed or joists must be minimised
  • Properties on heat pumps or all-electric tariffs where the running cost gap with wet UFH narrows

Limitations:

  • High running cost at the current UK electricity rate of approximately £0.25–0.28/kWh (June 2026 price cap)1
  • Not efficient as the sole heat source for large open-plan areas
  • Only effective as primary heat in well-insulated rooms (U-value 0.30 W/m²K or better)

Wet (hydronic) underfloor heating

Wet UFH circulates warm water, heated to 35–55°C rather than the 70–80°C needed for radiators, through 16 mm or 20 mm polyethylene pipes in a screed floor or stapled to a timber subfloor.2 A manifold distributes flow between zones, each with its own thermostat.

Best suited to:

  • Whole-house systems in new builds or major renovations where floors are open
  • Ground-floor extensions where a new screed is being poured
  • Properties with heat pumps: heat pumps operate at maximum efficiency (COP 3.0–4.5) when producing 35–45°C flow temperature, which is precisely what wet UFH needs

Limitations:

  • Higher installation cost and significant disruption: adding UFH to existing timber floors means either a liquid screed overlay (40–65 mm added floor level) or cutting into joists
  • Slower response times (1–4 hours from cold) make it better suited to systems left running continuously at a setback temperature rather than switched on-demand
  • Requires regular manifold maintenance, balancing, checking actuators, and bleeding circuits every 2–3 years

Installation Costs

Electric UFH installation costs

ApplicationLowTypicalHigh
Bathroom (4–6 m²), mat and thermostat£350£600£900
Kitchen (15–20 m²), mat and thermostat£900£1,500£2,200
Open-plan ground floor (40–60 m²)£2,500£4,200£6,500
Per m² (supply and fit)£50£85£150

Thermostats with Wi-Fi scheduling (Heatmiser neoStat, Honeywell T6R) add £80–£180 per zone but pay back quickly in reduced running hours.

Wet UFH installation costs

Wet system pricing varies considerably based on floor construction and whether a screed is being poured regardless (e.g. in an extension).

ScenarioLowTypicalHigh
Extension or new build (per m², into screed)£85£130£200
Retrofit to existing timber floor (per m², overlay plates)£120£165£240
Manifold, pump, actuators (2–4 zones)£600£950£1,600
Connection to existing boiler£400£700£1,200
Whole house (150 m² new build, ground floor + 1st floor)£14,000£22,000£35,000

Where wet UFH is added to an existing property’s timber floor using aluminium diffuser plates rather than a screed, the floor level rises by only 18–22 mm, manageable in most cases. Liquid anhydrite screed on an extension is typically included in the extension cost and adds only £15–£25/m² as a marginal cost for the UFH pipe within it.

Running Costs: Wet vs Electric

This is where the comparison becomes critical.

Electric UFH consumes roughly 100–150 W/m² at full load.3 At £0.27/kWh, a 20 m² bathroom-to-open-plan area running 6 hours/day would cost:

  • 20 m² × 0.12 kW/m² × 6 h = 14.4 kWh/day × £0.27 = £3.89/day, or roughly £117/month in peak winter

In practice, thermostats limit this significantly, a tiled bathroom mat set to switch off at 22°C won’t run continuously, but electric UFH as primary whole-house heating quickly becomes expensive.

Wet UFH with a gas combi boiler at 90% efficiency, heating to 45°C flow temperature, uses roughly 60–80 W/m² of heat input. At a gas rate of £0.06/kWh:

  • 20 m² × 0.07 kW/m² × 6 h ÷ 0.90 efficiency = 9.3 kWh/day × £0.06 = £0.56/day

Wet UFH with an air source heat pump (COP 3.5 at 45°C) brings electricity consumption down to roughly 0.02–0.03 kW/m² of electricity for the same heat output, making it the cheapest option per unit of heat delivered, though the heat pump installation itself costs £8,000–£16,000.

SystemApprox. running cost per m² per heating season (6 months)
Electric UFH (thermostatic, part-time use)£18–£45/m²
Wet UFH + gas boiler£3–£7/m²
Wet UFH + air source heat pump£2–£5/m²

Best Use Cases

UFH is unambiguously the right choice when:

  • You are pouring a new screed in an extension, the pipe adds minimal cost and the system is virtually free at that point
  • You are installing an air source heat pump and want to maximise efficiency, wet UFH at 35–45°C is the ideal pairing, and the Boiler Upgrade Scheme (£7,500 grant as of 2026) can offset heat pump costs45
  • You want to heat a tiled floor in a bathroom or kitchen as a comfort supplement, electric mats are cost-effective and simple here

UFH is harder to justify when:

  • You are retrofitting to a finished house with existing radiators and no other reason to open floors, unless it is part of a broader renovation
  • You have poor insulation (walls U-value above 0.45 W/m²K, loft below 270 mm mineral wool), sort the building fabric first6
  • The property is a rental let where you want quick, on-demand heat, UFH’s slow thermal mass works against intermittent occupancy

Building Regulations and Planning

Electric UFH is notifiable under Part P of Building Regulations if it involves a new circuit from the consumer unit, or an alteration to an existing circuit inside the special location, which runs from finished floor level to 2.25 m and 0.6 m out from the edge of the bath or shower tray, or 1.2 m from the shower head where there is no tray.7 It is the zone that is caught, not the whole room. Use a registered competent person (NICEIC, NAPIT or another scheme) to self-certify, or notify Building Control directly for approximately £300–£500 (minor building notice).

Wet UFH connected to a boiler is unregulated as a heating circuit change, but if you are also installing a new heat pump this requires MCS certification from the heat pump installer (required to claim the Boiler Upgrade Scheme grant).8 The heat pump installation itself must comply with Part L (energy efficiency) of Building Regulations.

There is no planning permission requirement for UFH in England, Scotland, or Wales under any normal circumstances.

Timescales

StageDuration
Electric mat installation (bathroom)Half a day
Electric mat installation (ground floor)1–2 days
Wet UFH manifold and pipework (extension, 50 m²)2–3 days (then wait for screed)
Anhydrite screed cure time before floor finish28 days minimum (28°C ambient)
Commissioning and balancingHalf a day

The screed curing period is the critical path in any wet UFH project, you cannot lay tiles, LVT, or engineered wood until the screed moisture content falls below 75% RH (checked with a calibrated hygrometer).9

Is It Worth It?

For a new extension with a new screed, wet UFH is almost always worth adding, the marginal cost is low and it pairs perfectly with a future heat pump. For a bathroom upgrade, electric mats deliver comfort for a reasonable upfront cost. For whole-house retrofit in an older property with joists and radiators, the disruption cost typically means the payback period is 12–20 years at current energy prices.

If you are planning a heat pump installation under the Boiler Upgrade Scheme, designing the ground floor around wet UFH from the outset is strongly recommended, it is the single most effective way to keep the heat pump’s flow temperature, and therefore its running costs, as low as possible.

References (9)

Figures in this note were checked against the sources below on 12 September 2026. Superscript numbers in the text point to them. Every source the site cites, by topic.

  1. 1technicalvery strongOfgem.RN-3YOULGOfgem's announcement of the energy price cap for 1 April to 30 June 2026. The cap is the unit rate and standing charge a running-cost comparison has to be built on, and it moves quarterly, so a heating cost quoted without its cap period is undated.
  2. 2technicalfairWhich?.RN-18I8HMWhich? on underfloor heating, the case for and against. Consumer-facing, so it frames the decision rather than supplying the design figures, which come from BS EN 1264.
  3. 3technicalfairWhich?, guidance.RN-ZYIPE1Which? on choosing underfloor heating: wet against electric, what suits a retrofit as opposed to a new floor, and how floor covering and insulation affect the result. A consumer body, so it is one step removed from the installation detail, and useful for framing the choice rather than for the numbers.
  4. 4technicalvery strongDepartment for Energy Security and Net Zero – GOV.UK.RN-13CX9GThe statutory notice setting the Boiler Upgrade Scheme grant categories and the amount payable for each. This is where the grant figure comes from, rather than an installer's summary of it.
  5. 5costvery strongGOV.UK.RN-9EFNVZA price, true at 2026-09. The grant values: £7,500 towards an air source heat pump, £7,500 towards a ground source heat pump including water source heat pumps and those on shared ground loops, and £5,000 towards a biomass boiler. A further £1,500 is available until March 2027 where the property is heated by oil or LPG and has no mains gas connection. Only one grant is available per property. Capacity limits are 45kWth for an individual system, 70kWth for multiple heat pumps and 300kWth for shared ground loops. Hybrid systems pairing a gas boiler with a heat pump are not eligible, and an existing low carbon heating system cannot be replaced under the scheme.
  6. 6technicalvery strongGOV.UK.RN-Z1K89ZAnnex G of the building regulations guidance, the summary table of which Approved Documents apply to which work. Useful as the index when a job touches several parts at once.
  7. 7technicalstrongInstitution of Engineering and Technology (IET).RN-BSB7FLThe IET's frequently asked questions on Part P in England and Wales. The clearest free statement of which domestic electrical work is notifiable, what a competent person scheme covers, and what a householder is left holding if the work was never notified.
  8. 8technicalvery strongOfgem.RN-IWJWPPOfgem's Boiler Upgrade Scheme page for installers. Sets out who may claim, the MCS certification required, and how the voucher is applied for on the householder's behalf, which is why the grant never passes through the homeowner's hands.
  9. 9technicalgoodContract Flooring Association (CFA).RN-H6JFPUContract Flooring Association guidance on measuring moisture in a floor with an in-situ probe. The method behind a relative humidity reading, and the reason a floor covering laid on a screed that has not been tested is a warranty problem waiting to happen.
  1. Changes to energy price cap between 1 April and 30 June 2026, Ofgem, accessed 12 September 2026. ofgem.gov.uk

  2. Underfloor heating pros and cons, Which?, accessed 12 September 2026. which.co.uk

  3. Three steps to getting the best underfloor heating for your home, Which?, accessed 12 September 2026. which.co.uk

  4. Notice of approved grant categories and values for the Boiler Upgrade Scheme, Department for Energy Security and Net Zero – GOV.UK, accessed 12 September 2026. gov.uk

  5. Apply for the Boiler Upgrade Scheme: What you can get, GOV.UK (Department for Energy Security and Net Zero), accessed 15 September 2026. Priced at 2026-09, so no calibration is needed. gov.uk

  6. ANNEX G, GOV.UK, accessed 12 September 2026. assets.publishing.service.gov.uk

  7. Frequently Asked Questions – Part P England and Wales, Institution of Engineering and Technology (IET), accessed 12 September 2026. electrical.theiet.org

  8. Boiler Upgrade Scheme (BUS) - Installers, Ofgem, accessed 12 September 2026. ofgem.gov.uk

  9. Guidance Note on Moisture Measurement – In-Situ Probe Method, Contract Flooring Association (CFA), accessed 12 September 2026. cfa.org.uk